## Closed-loop stability and dynamic tuning
|
||||
|
||||
The bit-level command above isolates the absolute epoch convention. The
|
||||
companion stability analysis connects that result to the fixed-point
|
||||
firmware/RTL PI model, replays the real GDOP and tracked-satellite history in
|
||||
`fusion/logs/gps_live_5min_20260713.csv`, and synthesizes only the telemetry
|
||||
that the repository did not capture:
|
||||
|
||||
```bash
|
||||
python3 -m pps_end_to_end_validation.stability_analysis
|
||||
python3 -m unittest \
|
||||
pps_end_to_end_validation/test_stability_analysis.py
|
||||
```
|
||||
|
||||
Generated results are in `output/stability/`:
|
||||
|
||||
- `stability_report.md`: real-data inventory, discrete poles, absolute phase
|
||||
wander, period jitter, dynamic parameter sweep, and recommendations;
|
||||
- `parameter_sweep.csv`: machine-readable results for every scenario/tuning;
|
||||
- `synthetic_telemetry.csv`: 5 Hz ABS_SAMPLE, REM_CODE_PHASE, corrected 125 MHz
|
||||
capture, HDOP/VDOP/TDOP/GDOP, C/N0, pseudorange noise, clock sigma/drift,
|
||||
oscillator and timing-error inputs.
|
||||
|
||||
The real capture contains 989 GDOP values and 990 tracked-satellite values
|
||||
(eight throughout), but no PPS phase/rate, ABS_SAMPLE, C/N0, TDOP/HDOP,
|
||||
pseudorange residual, oscillator temperature, or trusted-edge/TIC samples.
|
||||
The generated CSV labels its replacements as synthetic; it must not be read as
|
||||
board telemetry.
|
||||
|
||||
The current acquire, precision, and robust fixed-point poles are inside the
|
||||
unit circle at the 200 ms update rate, and the stress analysis observes no
|
||||
unlock. It also exposes an important metrics issue: cycle-to-cycle PPS period
|
||||
jitter can remain below 20 ns while absolute phase moves slowly through tens
|
||||
of nanoseconds. A physical 20 ns maximum therefore requires a common-clock
|
||||
time-interval-counter capture and cable/output-delay calibration; a p95 period
|
||||
jitter assertion or synthetic run cannot certify it.
|
||||
|
||||
The sweep includes the current coefficients, quieter/faster precision loops,
|
||||
a robust-noise guard, a larger Doppler-drift gain, and a quality-scheduled
|
||||
candidate. The generated report contains the current numerical comparison.
|
||||
No production constants are changed by the analysis.
|
||||
|
||||
## 20 ms diagnosis
|
||||
|
||||